Integrated solution · PIMA + Siemens KNX
20 m Beam Detector with Siemens KNX: PBI & Scene Control
Crossing a beam in a garden or passage triggers a defined smart-home action: path lighting, an indication or a sequence of commands. A wired integration of a transmitter/receiver pair, a dry-contact interface and a scene/event controller.
The key advantage: two beams for focused, stable detection
PIMA PROTECTOR TP-20 uses a powered transmitter and receiver to form an outdoor detection line of up to 20 m. Twin infrared beams are intended to reduce false alarms from small objects such as birds and leaves, subject to alignment and site conditions.
- Focused passage detection: TX and RX face each other across a defined detection line. A 15 m passage is within the selected model’s stated outdoor range of up to 20 m.
- Power planning for both units: Both TX and RX require continuous DC power. They may share one suitable supply connected in parallel: each side needs a power feed, not necessarily a separate PSU.
- Dry-contact scene triggering: The receiver relay contact reaches the PBI and then the N 305 event program to trigger lighting or indication.
TP-20 is the selected model. The PIMA family manual describes optical and response adjustment but does not include TP-20 in its model table. Do not transfer current ratings, angles, IP ratings or laser features from another variant without matching supplied-unit documentation. PIMA — official technical documents ↗
01 / POWER
The detector needs continuous power — the PBI does not power it
Both TX and RX require continuous DC power. The PIMA PROTECTOR family manual specifies 10–30 V DC, non-polar; confirm this range on the supplied TP-20. This reference design uses a separate regulated 12 V DC supply feeding both units in parallel. Only the voltage-free alarm contact connects to the PBI.
Can the Siemens 640 mA KNX supply also power the detector?
Siemens N 125/22, order number 5WG1125-1AB22, provides 29 V DC and an additional unchoked output. 29 V lies within the PROTECTOR family manual’s 10–30 V range. Assess a TP-20 auxiliary-output connection only after verifying the supplied revision, the full PSU output range and total current demand.
Never power the detector from the KNX bus conductors. An unchoked auxiliary-output design requires checks of SELV separation, protection, voltage drop and the shared current budget; do not assume another 640 mA is available. The main drawing retains a separate 12 V supply and does not approve a particular auxiliary-output installation.
Siemens N 125/22 — 640 mA ↗02 / COMPONENTS
The three components
PIMA PROTECTOR TP-20
Transmitter and receiver — beam crossing
An active twin-beam detector selected for this project with up to 20 m outdoor range. It can cover a 15 m passage. Optical range is not the permitted PBI contact cable length.
- Model / outdoor range
- PROTECTOR TP-20; up to 20 m
- Power in this design
- Continuous 12 V DC to TX and RX in parallel
- PIMA family manual
- 10–30 V DC, non-polar; verify on supplied TP-20
- PBI signal
- Receiver COM–NC dry contact; NC/NO per unit markings
- Cover contact
- Optional separate TAMPER input
- Current / environment
- Verify against supplied revision’s datasheet and markings
No pin numbers or current ratings are copied from another variant. The linked family manual does not list TP-20 in its model table; verify the actual harness, terminals and power requirements before installation.
Siemens UP 220/21
PBI — contact state to KNX

Order number 5WG1220-2AB21. Two configurable channels. In this design channel A reads the alarm contact; channel B may monitor the receiver cover tamper after its output is verified.
- Input type
- Potential-free contact; no external input voltage
- Power
- KNX bus-powered; no separate PBI supply
- Minimum input duration
- 50 ms
- Input cable length
- Maximum 10 m per channel; twisted, unshielded pair
- Location
- IP20; dry indoor installation
- Dimensions
- 42 × 42 × 8.5 mm; 11 mm at bus terminal
Install in a suitable indoor box. Do not share the box with 230 V devices or cables. Detector supply voltage must not be connected to PBI inputs.
Siemens N 305
Scene and event controller
Order number 5WG1305-1AB01. This is the controller selected for the reference design. It receives KNX telegrams and sends commands to actuators; it is not a lighting power output.
- Scene mode
- Up to 8 scenes, up to 8 groups per scene
- Event mode
- Up to 8 programs, up to 10 tasks per program
- Delays
- Scenes: 0–30 min; events: 0–120 min per task
- Mode selection
- Scene control or event programs, configured in ETS
- Supply / consumption
- KNX 21–30 V DC; 6 mA
- Installation
- DIN rail; 1 module, 18 mm wide; IP20
Select the operating mode and matching application in ETS. The event controller and the load actuator perform different functions; both are needed to operate a load.
03 / CONNECTIONS
Wiring diagrams — power, dry contact and KNX
Connections are identified by terminal function. A1/A2 and B1/B2 are drawing aliases for channel wire pairs, not printed pin numbers or wire colours. Match them to the supplied interface harness diagram. Line colours are a functional legend only.
Connection schedule
| From | To | Connection requirements |
|---|---|---|
| Regulated 12 V DC supply | TX POWER and RX POWER | Permanent parallel feeds; verify voltage at each unit under load. |
| Two RX ALARM NC terminals | UP 220/21 channel A input pair | Voltage-free contact only; no connection to detector 12 V or 0 V. |
| RX TAMPER contact, optional | UP 220/21 channel B input pair | Verify a potential-free contact; report separately from the lighting event. |
| N 125/22 choked KNX output | PBI, N 305 and actuator BUS terminals | Parallel bus wiring; observe the polarity marked on each device. |
| Actuator output | Compatible lighting or indication circuit | Load supply and protection belong to the electrical design; neither PBI nor N 305 powers the load. |
This is a reference interconnection design for the identified components, not a site-specific panel construction drawing. Check terminals, revisions and harness against the actual hardware before wiring. Mains and load wiring require an authorised electrician and the manufacturers’ instructions.
What else is required?
- A continuous regulated 12 V DC SELV supply, with protection and capacity for both units, tolerances and design margin. Verify TP-20 current demand against the supplied revision; do not use the previous detector’s figures.
- A dedicated KNX supply, such as Siemens N 125/22 640 mA, sized for all bus devices. Using the unchoked auxiliary output for detectors is a separate design option requiring verification.
- A load-compatible KNX actuator, KNX cable, contact pairs, power cables and suitable enclosures. PBI input wiring remains twisted, unshielded and limited to 10 m per channel under Siemens instructions.
- ETS commissioning, optical alignment and handover checks. Power-failure operation requires backup for both detectors and the control system.
04 / ETS & HANDOVER
Programming example: beam crossing switches path lighting
Example group addresses only — allocate unused addresses in the actual project. Event mode can send ON followed by OFF; verify how repeated crossings affect the running program.
| Example address | Signal | Data type | Proposed setting |
|---|---|---|---|
| 1/1/1 | Beam interrupted | 1 bit / DPT 1.001 | PBI A → N 305; 1 when NC opens, 0 on return to rest |
| 1/1/2 | Path light command | 1 bit / DPT 1.001 | N 305 → actuator; immediate ON, OFF after 120 seconds in this example |
| 1/1/3 | Cover tamper | 1 bit / DPT 1.005 | PBI B → tamper indication, if wired |
Configure channel A for NC contact-state monitoring rather than long-press operation. In N 305 select an event program triggered by value 1. Decide whether repeated telegrams restart a sequence, are ignored while running or extend a staircase timer in the actuator. Do not promise automatic retriggering without checking the selected application.
Handover checks
- Measure continuous TX and RX supply, including cable voltage drop, and verify it stays within the detector limits.
- Align TX/RX over a clear line of sight and perform crossing tests at different points and walking speeds.
- Verify NC closed at rest, open on detection and return to rest; inspect telegrams in ETS.
- Test lighting, switch-off delay, repeated crossings, cover tamper and recovery after a supply failure.
- Record models, group addresses, timing and limitations. A single beam pair does not establish direction or count people.
Installation conditions and limits
Mount TX and RX on stable surfaces with a clear line of sight, following PIMA instructions and the rating of the supplied units. Match enclosures and cables to sunlight and water exposure. This integration provides automation and indication; it is not a gate safety sensor or a replacement for a supervised alarm system. A simple NC loop cannot distinguish a crossing from a broken wire and does not guarantee short-circuit detection.
Frequently asked questions
Does the detector work without a power supply?
No. Both TX and RX need continuous DC power. The PBI reads a dry contact and does not supply detector operating power.
Can the TP-20 use a Siemens 29 V supply?
An unchoked auxiliary output is an option to assess after verifying the supplied revision supports the full voltage range and the current budget is sufficient. Do not connect detector power to bus conductors. The drawing uses a separate 12 V supply.
Are all components made by Siemens?
No. The detector is PIMA PROTECTOR TP-20; the PBI and N 305 are Siemens. This is an I Feel integration solution.
Is 20 m the permitted cable length to the PBI?
No. Up to 20 m is the outdoor optical range. Receiver-to-UP 220/21 contact wiring is limited to 10 m per channel.
05 / TECHNICAL SOURCES
Technical sources and specification limits
TP-20 and an outdoor range of up to 20 m are the project selection. The official PIMA document below is a family manual: it specifies 10–30 V DC, powered TX/RX and NC/NO relay contacts, but its model table does not include TP-20. Revision-specific current, IP, response-time and terminal-number claims are therefore not assigned here. Match the design to the supplied units’ documents and markings before installation. Siemens documents cover the exact models listed on this page.
- PIMA PROTECTOR — official family installation manual ↗
- PIMA — official download centre, PROTECTOR-TP ↗
- Siemens UP 220/21 — Operating and Mounting Instructions (04/2020) ↗
- Siemens N 305 — Technical Product Information (04/2010) ↗
- Siemens N 305 — Application 750006 (10/2016) ↗
- Siemens N 125/22 — 29 V DC, 640 mA, auxiliary output ↗
Planning a beam-triggered scene?
Send the optical distance, receiver-to-indoor-PBI cable distance, KNX PSU model and required actions. We will specify power, components and commissioning.